Clean Room

/

Clean Room Filtration Units

/

Fresh Heaven MAXX O Power Laminar Airflow Unit
Fresh Heaven MAXX O Power Laminar Airflow Unit
Fresh Heaven MAXX O Power Laminar Airflow Unit

FläktGroup

Fresh Heaven MAXX O Power Laminar Airflow Unit

Laminar airflow unit ensures full filtration of air supplied by an air-handling unit and protects the operating area around a patient without dead zones.

Overview

Fresh Heaven MAXX O POWER ensures full filtration of air supplied by an air-handling unit and mixed with recirculated clean room air, thereby protecting the operating theater area around a patient.

• Complete filtration of operating area with a function to mix supply air (from AHU) and recirculating air
• Easy installation, maintenance and disinfection
• Low initial pressure drop of HEPA filters
• Tailored dimensions with LED lighting and control unit

Product description

The Fresh Heaven MAXX O POWER laminar air-flow units are part of the structural arrangement of the suspended ceiling of an operating theater.

• Operating principle

Fresh Heaven MAXX O POWER unit supplies clean air in a low-turbulent and vertical flow into an operating room. Thus, the contamination of sensitive areas and equipment can be held at a minimised level.

The Fresh Heaven MAXX O POWER is equipped with are circulating POWER module which sucks air within a room. Recirculated air from the POWER module can be mixed with fresh air supplied by AHU (20-30%) in the mixing chamber. The mixed air is then delivered into the pressure chamber, filtered, and diffused into the operating area.

Fresh Heaven MAXX O POWER unit design provides space in the centre for surgical lighting installation. The laminarizer's circumference is lit by LED lighting integrated into the casing's sides. To enhance laminar airflow and minimise air turbulence, a PET-G soft wall can be integrated around the entire circumference of the unit.

There are available 5 sizes, and an air volume is given at a velocity of 0.30 m/s:

• A – 320 x 320 x 45 cm, air volume 11 059 m3/h
• B – 300 x 300 x 45 cm, air volume 9 720 m3/h
• C – 300 x 240 x 45 cm, air volume 7 776 m3/h
• D – 300 x 200 x 45 cm, air volume 6 480 m3/h
• E – 240 x 240 x 45 cm, air volume 6 221 m3/h

Filters offer includes HEPA filters in an aluminium frame 104 mm high. The filter features a gel gasket and protective grid on its clean air side. The filters are available in following filtration classes:

• H13
• H14

Pre-filter for POWER module:

• F7 filtration class
• pre-filters not part of PCB, PCS and PCU POWER module configurations

Casing:

• Varnished steel RAL 9010
• Stainless steel V2A ~AISI304

Outlets:

• Single-layer PES (polyester) fabric
• Double-layer with differential airflow (higher air velocity in the central area, measuring 100 x 200 cm)

POWER modules - for improved acoustic features the chamber of the POWER fan module is lined with mineral wool slabs. There are available following POWER modules:

• PU4 – installed in a false ceiling, suction is performed through the grille on bottom side of PU4.
• PCB – installed in a false ceiling, suction is performed through connecting ducts (diameter 355 mm) on the back side of PCB connected to e.g. CGx installed in false ceiling or lower/upper wall corners.
• PCS – installed in a false ceiling, suction is performed through connecting ducts (diameter 355 mm) on lateral sides of PCS connected to e.g. CGx installed in false ceiling or lower/upper wall corners.
• PCU – installed in a false ceiling, suction is performed through OMF grilles (above floor and optionally under ceiling) connected to rectangular channels in OT+ partition/facing.
• PTI – recirculation PTI towers installed in operating room, suction is performed through grilles in towers (above floor)
• PTE – recirculation PTE towers installed outside operating room(in an adjoining room), suction is performed through grilles in towers (above floor)

Unit controls and selectable components:

• Control panel – Siemens Logo! PLC with display enables to switch on/off the unit, switchover to economy mode, activate and deactivate of lighting, alarm (fan failure,clogged HEPA filters or pre-filters)
• MODBUS - Customers can use the MODBUS interface of a BMS to establish connection and regulate a FHMO.P unit with a central-plant air handling unit.
• Differential-pressure switch – monitors differential pressure of filters (pressure connection via two plastic tubes), can be equipped with connections to a filter-exchange indicator
• Filter-exchange indicator – may be installed in the central passage of the low-turbulence flow unit to signal filter clogging via red LED
• Lighting- LED lighting can be installed around the entire perimeter of the laminar air-flow field
• Border soft wall as PET-G screen - to minimise air turbulences, maximise laminar air-flow zone and prevent reduction in its cross-section - a soft wall (curtain)can be integrated on the entire circumference of the unit. Standard width 30 cm.
• Air-mixing module – is designed for supply of fresh air and for its uniform mixing with recirculated air.
• Sound attenuator – made of lacquered steel, lined with mineral wool slabs (installed between FHMO inlet and POWER module)
• Junction duct - Performed in galvanised steel (length is determined by the project requirements)
• Cooling assembly - PTE and PTI can be equipped with an air-water heat exchanger
• Exhaust-air panels RA/MA (clean room wall panel featuring an OMS grille with adjustment on the bottom side and a round socket for duct connection on the top side)
• Exhaust-air ducts for OT+ panels
• OMS/OMN/OMF grilles
• CGxair outlets with HEPA filters

Key facts

• Air flow speed 0.25 - 0.38 m/s
• Dimensions 2.40 m x 2.40 m (min.) and 3.20 m x 3.20 m (max.)
• 5 model sizes
• Central passage for mounting surgical lighting
• Operating mode: air supplied by AHU (20-30% of total volume)and mixed with recirculated air
• Casing material in varnished steel sheet RAL 9010 or stainless steel sheet V2A / AISI 304
• POWER module with EC fans and F7 pre-filter
• Air-mixing module for supply and recirculating air
• Filter seal as gel-type
• Outlets as single-layer laminarizer or double-layer laminarizer (for differential air flow) in PES fabric on aluminium frame
• Various accessories, e.g. UV-C lamps, sound attenuators,supply and air-extraction ducts, condensation-free cooling coil, etc.
• Uniform air flow distribution

Features

• UV-C lamps: Decrease the spread of airborne pathogens such as virus and bacteria with the proven and effective UV-C modules.
• Modular setup: Modular setup enables to configure the unit at maximum flexibility.
• Air-mixing function: AHU located outside the operating theater supplies a portion of the total air volume, typically ranging from 20-30%. Pre-treated supply air from the central unit is delivered to the mixing chamber of Fresh Heaven Maxx O POWER units. There, it mixes with pre-filtered (F7) recirculated air extracted from the operating theater. The unit is equipped with flaps to prevent backflow through pre-filters during fan or power failure.
• LED lighting: LED lighting can be installed around the entire perimeter of the laminar air-flow field. Different colours can signal working mode of operating theater or laminar ceiling (e.g. standard white colour is used for day mode, red for night/reduced mode).